Why ring circuits worried people
Most UK homes run their sockets on ring final circuits, usually protected by a 32 A breaker, with the cable sized on the assumption that current from the consumer unit splits both ways round the ring. A plug-in kit pushes power in at one socket instead. With a few appliances running, the cable near that socket can carry more current than the breaker ever sees, because some of it is coming from the panel on your balcony and not from the consumer unit. Nothing trips, and the cable is the part that takes the strain.
How the spec deals with it
The government had these devices tested on UK circuits and found them safe within defined limits. Those limits are the core of the spec:
- Output is capped at 800 VA, and the current at the plug must not go above 3.5 A under any test condition.
- Only one plug-in device per household final ring circuit. The network notification rules (G98) currently go further and allow only one device per household.
- The panels themselves can add up to 2,000 W, but above 960 W the maker has to tell you to consider getting your installation checked.
- The plug must be a moulded BS 1363 plug with a fuse of no more than 5 A.
- No extension leads, no multi-way adaptors, no travel adaptors and no RCD adaptors. Straight into a wall socket.
- The device must not interfere with the RCD protection upstream, and the instructions tell you to press the test button on your RCBO now and then while the kit is producing. If it does not trip, call an electrician.
- No batteries. The spec says these devices are not to be used with a battery storage system.
Yes, if the kit is compliant and you follow those conditions. The 3.5 A limit is what keeps the extra current small enough for a ring. The things that make it unsafe are the ones the spec bans: a second kit on the same circuit, a non-compliant kit bought from abroad with an adaptor in the box, an extension lead running out to the balcony, or a circuit with no working RCD.
Before you plug in
- Check the kit is registered on the ENA type test register. Makers have to register before selling, and anything sold here with a European plug and an adaptor is not a compliant kit.
- Check your consumer unit has RCD or RCBO protection on the socket circuits. Older boards often do not.
- Notify your network operator. It is a notification, not an application, and you have to tell them again if you disconnect the kit for good.