Here is how to work out what you have, roughly in the order an electrician would look at it.
1. Open the consumer unit and see which of these you have
Fuses rather than switches. A row of white or ceramic fuse carriers you can pull out, or cartridge fuses, with no test buttons anywhere. This is an old fuse board, and with either kind you should have an electrician look before buying anything. The specification says older fuse protection needs checking and, where needed, upgrading by a professional, and the Energy Saving Trust says not to install at all if you have rewireable fuses.
A row of small switches with one or two larger switches that have a test button. The small switches are MCBs, which only protect against overcurrent. The larger ones marked T or Test are RCDs, each covering a group of circuits. The specification says this arrangement may be acceptable, but notes that it is still waiting on government testing to confirm it.
A switch for every circuit, each with its own test button. These are RCBOs, an MCB and an RCD in one device. This is what the specification calls modern residual current protection, and it is the setup the rules are written around.
If your board has no labels, looks old, or you are not sure which of these it is, the specification's advice is to have it inspected before going any further.
2. Find the type printed on the RCD or RCBO
Every RCD and RCBO is marked with a type, usually as a small symbol and often in text as well.
- Type AC: a single wave symbol. Detects ordinary AC leakage only.
- Type A: a wave plus a half wave symbol. Also detects pulsing DC.
- Type F and Type B: extra symbols alongside the Type A ones. Less common in houses. Type B also detects smooth DC.
3. Which way the power flows
Some RCDs and RCBOs are designed to be fed from one side only. With a plug-in kit running, power arrives from the circuit side as well as from the supply side. Electricians point out that a one way device fed from the wrong side can be damaged, and that the damage can remain after the kit is unplugged. You usually cannot tell this from the front of the board. The device's datasheet or an electrician can, which is one more reason the IET says most householders cannot judge suitability just by looking.
4. If you rent
In England, private landlords have to have the electrics inspected at least every five years and give tenants a copy of the report, the EICR. Scotland and Wales have similar five yearly checks. Ask for the latest one. The schedule of circuits in that report lists each protective device and its type, which answers most of this page without opening anything. You still need your landlord's agreement for the kit itself.
5. The test you should keep doing
Once the kit is in, the specification asks you to test the RCBO from time to time by pressing its test button while the kit is producing power. It should trip straight away. If it does not, unplug the kit and talk to an electrician about replacing the device. The Energy Saving Trust suggests doing this every six months on a bright day. Pressing the button switches off everything on that circuit, or the whole group if you have a shared RCD, so save your work first and check the freezer comes back on afterwards.
6. The label
Compliant kits come with a durable label for the consumer unit. Stick it on or next to the board so that anyone who works on it later knows there is a generator on one of the circuits. If the board is ever replaced or moved, the label has to go on the new one.
When to get an electrician before you buy
- You have rewireable or cartridge fuses.
- The board is unlabelled, old, or you cannot tell what is protecting the socket you want to use.
- The device on that circuit is marked Type AC.
- Your panels add up to more than 960 W, the point where the specification says to consider a professional assessment.
- The test button does not trip the device, now or at any later check.
Last updated: October 14, 2026